Per E-Mail benachrichtigen, sobald dieses Produkt verfügbar ist
- Beschreibung
- Reviews
- Versand & Zahlung
Configured for isolated low-level analog signal acquisition in the Modicon X80 platform, the Schneider Electric BMXART0414 (BMXART0414 Analog Input Module) provides four isolated input channels with configurable voltage, resistance, temperature probe, and thermocouple measurement functions. The module uses a 40-way connector and occupies one rack slot.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | BMXART0414 |
| Brand | Schneider Electric |
| Product Type | Analog isolated low level input module |
| Series | Modicon X80 |
| Origin | US |
| Number of Inputs | 4 |
| Input Level | Low level |
| Input Isolation | Isolated |
| Electrical Connection | 40-way, 1 connector |
| Analog Input Type | Voltage, resistance, temperature probe, thermocouple |
| Voltage Ranges | +/- 40 mV, +/- 80 mV, +/- 160 mV, +/- 320 mV, +/- 640 mV, +/- 1.28 V |
| Resistance Inputs | 400 Ohm and 4000 Ohm, 2-wire, 3-wire, or 4-wire |
| Analog/Digital Conversion | Sigma delta, 16 bits |
| Analog Input Resolution | 15 bits + sign |
| Common Mode Rejection | 120 dB at 50/60 Hz |
| Differential Mode Rejection | 60 dB at 50/60 Hz |
| Cold Junction Compensation | External by Pt100 probe |
| Digital Filtering | First order digital filtering |
| Nominal Read Cycle | 400 ms with temperature probe; 200 ms with thermocouple |
| Isolation Voltage | 1400 V DC between channels and bus; 750 V DC between channels; 750 V DC between channels and ground |
| Maximum Wiring Resistance | Up to 500 Ohm depending on sensor type and wiring configuration |
| Measurement Resolution | 0.1 deg C for supported temperature probe and thermocouple configurations |
| Recalibration | Internal |
| Status Indication | RUN, channel diagnostic, ERR, and I/O LEDs |
| Weight | 0.135 kg |
| Operating Temp | 0 to 60 deg C |
| Storage Temp | -40 to 85 deg C |
| Relative Humidity | 5 to 95% at 55 deg C, non-condensing |
| IP Rating | IP20 |
| Vibration Resistance | 3 gn |
| Shock Resistance | 30 gn |
| Power Consumption | 150 mA at 3.3 VDC; 40 mA at 24 VDC |
| Latest Firmware | SV2.3 |
| Certifications | EAC, RCM, UL, Merchant Navy, CSA, CE |
| Standards | IEC 61131-2, IEC 61000-6-4, IEC 61000-6-2, EN 61010-2-201 |
Industrial Control and I/O Characteristics
The BMXART0414 provides four independently isolated analog acquisition channels within one Modicon X80 rack slot. Its low-level ranges extend from +/- 40 mV to +/- 1.28 V, while resistance and temperature configurations support multiple 2-wire, 3-wire, and 4-wire sensor arrangements. The module performs 16-bit sigma-delta conversion with a stated analog resolution of 15 bits plus sign.
Channel and bus isolation are specified at 1400 V DC, while channel-to-channel and channel-to-ground isolation are specified at 750 V DC. Common-mode rejection is 120 dB at 50/60 Hz and differential-mode rejection is 60 dB at 50/60 Hz.
The module supports internal recalibration and first-order digital filtering. Temperature and thermocouple configurations use external Pt100-based cold junction compensation where specified. The source lists SV2.3 as the latest firmware version for the product.
Frequently Asked Questions
Q: How many analog channels does the BMXART0414 provide?
A: The module provides four isolated low-level analog input channels.
Q: What signal types can be connected to the BMXART0414?
A: Depending on configuration, the inputs support low-level voltage, 400 Ohm and 4000 Ohm resistance, temperature probes, and thermocouples.
Q: What is the specified module power consumption?
A: The source specifies 150 mA at 3.3 VDC and 40 mA at 24 VDC.
Field Installation Guidelines
Install the BMXART0414 in its designated Modicon X80 rack slot and connect the field wiring through the specified 40-way connector. Confirm the configured input type before wiring each channel because voltage, resistance, temperature probe, and thermocouple configurations use different electrical measurement arrangements.
For low-level analog signals, route sensor wiring separately from high-current power conductors and switching circuits. Maintain appropriate shielding and grounding practices for the installation environment. Use the specified wiring configuration for 2-wire, 3-wire, or 4-wire resistance and temperature sensors.
Verify the selected input range against the connected sensor before commissioning. For thermocouple and temperature measurements, confirm the external Pt100 cold junction compensation arrangement where applicable. Check RUN, channel diagnostic, ERR, and I/O status indicators during startup. The module has IP20 protection and an operating temperature range of 0 to 60 deg C.
Zahlung: T/T, Western Union.
Versandhafen: Xiamen.
Lieferzeit: In der Regel 1–3 Werktage nach Bestätigung der Zahlung (je nach Lagerbestand).
Weltweiter Versand: Wir versenden Teile für die industrielle Automatisierung an Kunden weltweit. Die Frachtkosten werden mit Ihrem RFQ angegeben.
Häufig gestellte Fragen
Häufige Fragen zu Angeboten, Versand, Garantie und RückgabenKlicken Sie auf der Produktseite auf Angebot anfordern und teilen Sie uns die Teilenummer, die benötigte Menge und das Zielland mit. Unser Vertriebsteam antwortet mit der aktuellen Verfügbarkeit, dem Preis und der voraussichtlichen Lieferzeit.
Vorrätige Artikel werden normalerweise nach Zahlung und Auftragsbestätigung vorbereitet. Die meisten Bestellungen werden von unserem Lager in China versandt, wobei der Versandort je nach aktuellem Lagerbestand variieren kann.
Ja. Wir versenden Teile für die industrielle Automatisierung an Kunden weltweit. Versandkosten und Lieferzeit hängen vom Bestimmungsort, dem Paketgewicht, der Produktgröße und den örtlichen Einfuhrbestimmungen ab.
Wir nutzen in der Regel DHL, FedEx, UPS und andere internationale Kurierdienste. Der Versanddienstleister kann je nach Zielort, Liefergeschwindigkeit, Sendungsgröße und Kundenanforderungen ausgewählt werden.
Unsere Produkte sind grundsätzlich durch eine 12-monatige Garantie abgedeckt. Für berechtigte Produkte ist außerdem eine Rückgabe gemäß unserer 30-Tage-Erstattungsrichtlinie möglich. Bitte kontaktieren Sie unser Team, bevor Sie einen Artikel zurücksenden, um die geltenden Bedingungen und Rücksendeanweisungen zu bestätigen.
Das könnte Ihnen auch gefallen
Blogbeiträge
Neuigkeiten zur industriellen Automatisierung, technische Anleitungen und Produktneuheiten.