
Per E-Mail benachrichtigen, sobald dieses Produkt verfügbar ist
- Beschreibung
- Reviews
- Versand & Zahlung
Configured for temperature, voltage, resistance, and thermocouple measurement in the Modicon X80 platform, the Schneider Electric BMXART0814 (BMXART0814 analog input module) provides eight isolated low-level analog input channels with 15 bits + sign resolution. It supports RTD, thermocouple, resistance, and voltage input ranges with external cold junction compensation by Pt100 probe.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | BMXART0814 |
| Brand | Schneider Electric |
| Series | Modicon X80 |
| Product Type | Analog input module |
| Analog Inputs | 8 |
| Input Level | Low level |
| Channel Isolation | Isolated between channels |
| Input Types | Voltage, resistance, RTD, thermocouple |
| Analog Input Resolution | 15 bits + sign |
| A/D Conversion | Sigma delta, 16 bits |
| Voltage Ranges | +/- 40 mV, +/- 80 mV, +/- 160 mV, +/- 320 mV, +/- 640 mV, +/- 1.28 V |
| Resistance Inputs | 400 Ohm and 4000 Ohm, 2-wire, 3-wire, or 4-wire |
| RTD Inputs | Cu 10, Ni 100, Ni 1000, Pt 100, Pt 1000 |
| Thermocouple Types | B, E, J, K, L, N, R, S, T, U |
| Cold Junction Compensation | External by Pt100 probe |
| Nominal Read Cycle | 400 ms with temperature probe; 200 ms with thermocouple |
| Common Mode Rejection | 120 dB at 50/60 Hz |
| Differential Mode Rejection | 60 dB at 50/60 Hz |
| Digital Filtering | First order |
| Measurement Resolution | 0.1 deg C for supported temperature inputs |
| Maximum Wiring Resistance | Up to 500 Ohm depending on sensor and wiring configuration |
| Electrical Connection | 40-way, 2 connectors |
| Current Consumption | 150 mA at 3.3 VDC; 50 mA at 24 VDC |
| Weight | 0.165 kg |
| Operating Temp | 0 to 60 deg C |
| Storage Temp | -40 to 85 deg C |
| Relative Humidity | 5 to 95% at 55 deg C, non-condensing |
| IP Rating | IP20 |
| Vibration Resistance | 3 gn |
| Shock Resistance | 30 gn |
| Operating Altitude | 0 to 2000 m; 2000 to 5000 m with derating |
| Recalibration | Internal |
| Open Circuit Detection | Supported for specified RTD and thermocouple inputs |
| Status Indication | RUN, channel diagnostic, ERR, and I/O LEDs |
| Certifications | CE, EAC, UL, CSA, Merchant Navy, RCM |
| Standards | IEC 61131-2, IEC 61000-6-4, IEC 61000-6-2, EN 61010-2-201 |
| Protective Treatment | Standard version |
The module specifications identify eight isolated inputs, low-level input operation, 15 bits + sign resolution, and a 150 mA current consumption at 3.3 VDC. The environmental ratings and physical weight are specified as IP20, 0 to 60 deg C operating temperature, and 0.165 kg net weight.
I/O Density and Signal Conditioning
The BMXART0814 provides eight analog channels within a Modicon X80 module. The input circuitry accepts multiple low-level voltage ranges, resistance configurations, RTD types, and thermocouple types. Channel-to-channel isolation separates the individual input circuits. The module applies first-order digital filtering and provides common-mode rejection of 120 dB and differential-mode rejection of 60 dB at 50/60 Hz.
For temperature measurement, cold junction compensation is performed externally using a Pt100 probe. The specified measurement and temperature-drift values vary according to the selected sensor or input range. Internal recalibration and open-circuit detection are provided for the supported sensor types.
Frequently Asked Questions
Q: How many analog channels does the BMXART0814 provide?
A: It provides 8 analog input channels with channel-to-channel isolation.
Q: What power consumption is specified for the module?
A: The module consumes 150 mA at 3.3 VDC and 50 mA at 24 VDC.
Q: How is cold junction compensation implemented?
A: Cold junction compensation is external and uses a Pt100 probe.
Field Installation Guidelines
- Install the module in the compatible Modicon X80 rack and secure the module mechanically before connecting field wiring.
- Use the specified 40-way connector arrangement for electrical connections.
- Separate low-level analog and thermocouple wiring from high-current power and switching conductors where practical.
- Maintain correct sensor wiring configuration for 2-wire, 3-wire, or 4-wire resistance and RTD measurements.
- Apply shield termination according to the installation grounding scheme and avoid creating unintended ground loops.
- For thermocouple channels, use the appropriate thermocouple wiring and verify the external Pt100 connection required for cold junction compensation.
- Confirm the selected input range and sensor type before commissioning each channel.
- Observe the IP20 enclosure limitation and install the module inside an enclosure providing the required environmental protection.
- Keep ambient operating temperature within 0 to 60 deg C and account for altitude derating above 2000 m.
Zahlung: T/T, Western Union.
Versandhafen: Xiamen.
Lieferzeit: In der Regel 1–3 Werktage nach Bestätigung der Zahlung (je nach Lagerbestand).
Weltweiter Versand: Wir versenden Teile für die industrielle Automatisierung an Kunden weltweit. Die Frachtkosten werden mit Ihrem RFQ angegeben.
Häufig gestellte Fragen
Häufige Fragen zu Angeboten, Versand, Garantie und RückgabenKlicken Sie auf der Produktseite auf Angebot anfordern und teilen Sie uns die Teilenummer, die benötigte Menge und das Zielland mit. Unser Vertriebsteam antwortet mit der aktuellen Verfügbarkeit, dem Preis und der voraussichtlichen Lieferzeit.
Vorrätige Artikel werden normalerweise nach Zahlung und Auftragsbestätigung vorbereitet. Die meisten Bestellungen werden von unserem Lager in China versandt, wobei der Versandort je nach aktuellem Lagerbestand variieren kann.
Ja. Wir versenden Teile für die industrielle Automatisierung an Kunden weltweit. Versandkosten und Lieferzeit hängen vom Bestimmungsort, dem Paketgewicht, der Produktgröße und den örtlichen Einfuhrbestimmungen ab.
Wir nutzen in der Regel DHL, FedEx, UPS und andere internationale Kurierdienste. Der Versanddienstleister kann je nach Zielort, Liefergeschwindigkeit, Sendungsgröße und Kundenanforderungen ausgewählt werden.
Unsere Produkte sind grundsätzlich durch eine 12-monatige Garantie abgedeckt. Für berechtigte Produkte ist außerdem eine Rückgabe gemäß unserer 30-Tage-Erstattungsrichtlinie möglich. Bitte kontaktieren Sie unser Team, bevor Sie einen Artikel zurücksenden, um die geltenden Bedingungen und Rücksendeanweisungen zu bestätigen.
Das könnte Ihnen auch gefallen
Blogbeiträge
Neuigkeiten zur industriellen Automatisierung, technische Anleitungen und Produktneuheiten.
