The BMXDAO1605 is a 16-channel AC triac discrete output module in the Schneider Electric Modicon X80 range. It switches AC loads through solid-state outputs, with a rated operating voltage range of 100 to 240 V AC. The module provides individual channel switching, resistive-load response specifications, and external fast-blow fuse protection.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | BMXDAO1605 |
| Brand | Schneider Electric |
| Product Range | Modicon X80 |
| Product Type | Discrete Output Module |
| Number of Outputs | 16 |
| Output Technology | Triac |
| Rated Output Voltage | 100 to 240 V AC |
| Output Voltage Range | 85 to 288 V AC |
| Current per Channel | 0.6 A |
| Output Current Limits | 0.025 to 4.8 A |
| Inrush Current | 20 A |
| Typical Current Consumption | 100 mA at 3.3 V DC |
| Output Response Time | 10 MOhm at 500 V DC |
| Dielectric Strength | 2830 V AC, 50/60 Hz, 1 min |
| Protection | 1 external fast-blow fuse |
| Protection Rating | IP20 |
| Protective Treatment | Standard version |
| MTBF | 1,800,000 h |
| Relative Humidity | 5 to 95% at 55 deg C, non-condensing |
| Package Weight | 203 g |
| GTIN | 3595863966954 |
Output Operation and Protection
The BMXDAO1605 uses triac switching devices to control AC loads. Unlike electromechanical relay outputs, triac outputs have no mechanical contacts. Their solid-state switching characteristics make the module suitable for AC discrete control circuits where the load current and voltage remain within the specified operating limits.
The specified output response time of 1.011 ms applies to resistive-load activation and deactivation. Actual switching behavior with inductive or other non-resistive loads may differ and should be checked against the applicable load requirements.
Electrical Protection and Isolation
The module specifies one external fast-blow fuse as its output protection arrangement. Fuse selection and installation must account for the connected load and the applicable channel current limits. The 20 A inrush current specification should also be considered when evaluating loads with high starting currents.
The insulation resistance and dielectric strength ratings describe electrical isolation performance under the stated test conditions. They should not be interpreted as permission to exceed the rated operating voltage.
Modicon X80 Platform
The BMXDAO1605 belongs to the Modicon X80 common module platform, which is used with Modicon M340 and M580 Programmable Automation Controllers. Its platform classification identifies the product family; the actual rack configuration and controller compatibility should be checked against the relevant hardware configuration documentation.
Operating Conditions and Load Distribution
The output current must be assessed at both channel and group level. The module's total permissible load depends on the number of energized channels and ambient temperature; the individual channel rating should not be treated as an allowance to operate all 16 outputs simultaneously at maximum current.
For a 220 V AC resistive-load example, Schneider Electric's X80 module documentation specifies the following load conditions:
- At 0 to 40 deg C, 16 channels at 0.3 A each correspond to a total load of 4.8 A.
- Above 40 deg C, output loading must follow the specified temperature derating curve.
- At 60 deg C, the maximum total current is reduced to approximately 2.9 A, corresponding to 10 channels at 0.3 A or 16 channels at approximately 0.18 A.
These limits are important when distributing loads across the output groups and checking cabinet operating temperature.
Frequently Asked Questions
Q: What type of loads can the BMXDAO1605 switch?
A: It uses triac outputs for AC switching within the specified 100 to 240 V AC operating range. It is not a DC transistor output module.
Q: Does each output support 0.6 A continuously?
A: The 0.6 A figure is listed in Schneider Electric's product information, but it should not be interpreted as 0.6 A simultaneously on all 16 channels. Total current and channel loading are subject to group limits and temperature derating.
Q: What external protection is required?
A: The module specifies external fast-blow fuse protection. Schneider's connection documentation identifies a 3 A fast-blow fuse for each four-channel group; confirm the applicable wiring diagram and load requirements before installation.
Zahlung: T/T, Western Union.
Versandhafen: Xiamen.
Lieferzeit: In der Regel 1–3 Werktage nach Bestätigung der Zahlung (je nach Lagerbestand).
Weltweiter Versand: Wir versenden Teile für die industrielle Automatisierung an Kunden weltweit. Die Frachtkosten werden mit Ihrem RFQ angegeben.
Häufig gestellte Fragen
Häufige Fragen zu Angeboten, Versand, Garantie und RückgabenKlicken Sie auf der Produktseite auf Angebot anfordern und teilen Sie uns die Teilenummer, die benötigte Menge und das Zielland mit. Unser Vertriebsteam antwortet mit der aktuellen Verfügbarkeit, dem Preis und der voraussichtlichen Lieferzeit.
Vorrätige Artikel werden normalerweise nach Zahlung und Auftragsbestätigung vorbereitet. Die meisten Bestellungen werden von unserem Lager in China versandt, wobei der Versandort je nach aktuellem Lagerbestand variieren kann.
Ja. Wir versenden Teile für die industrielle Automatisierung an Kunden weltweit. Versandkosten und Lieferzeit hängen vom Bestimmungsort, dem Paketgewicht, der Produktgröße und den örtlichen Einfuhrbestimmungen ab.
Wir nutzen in der Regel DHL, FedEx, UPS und andere internationale Kurierdienste. Der Versanddienstleister kann je nach Zielort, Liefergeschwindigkeit, Sendungsgröße und Kundenanforderungen ausgewählt werden.
Unsere Produkte sind grundsätzlich durch eine 12-monatige Garantie abgedeckt. Für berechtigte Produkte ist außerdem eine Rückgabe gemäß unserer 30-Tage-Erstattungsrichtlinie möglich. Bitte kontaktieren Sie unser Team, bevor Sie einen Artikel zurücksenden, um die geltenden Bedingungen und Rücksendeanweisungen zu bestätigen.
Das könnte Ihnen auch gefallen
Blogbeiträge
Neuigkeiten zur industriellen Automatisierung, technische Anleitungen und Produktneuheiten.