
Notificado por e-mail quando este produto estiver disponível
- Descrição
- Reviews
- Envio e pagamento
Configured for OPC UA client communication and IT network data exchange in the Modicon M580 platform, the Schneider Electric BMENUA0100 (BMENUA0100 communication module) provides an embedded OPC UA server with Ethernet connectivity, backplane transparency, and diagnostic communication services.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | BMENUA0100 |
| Brand | Schneider Electric |
| Series | Modicon M580 |
| Product Type | Ethernet communication module |
| Application | OPC UA server and IT control network |
| OPC UA Standard | OPC UA V1.03 |
| OPC UA Clients | 10 maximum |
| Monitored Items | 50,000 maximum standard sampling; 2,000 maximum fast sampling |
| Maximum Nodes | 100,000 |
| Ethernet Port | 1 x RJ45, 10/100/1000 Mbit/s |
| Ethernet Medium | Double-shielded twisted pair |
| Backplane | Ethernet and X-bus |
| Maximum Modules per Rack | 2 |
| Power Supply | Internal rack power |
| Current Consumption | <= 140 mA at 24 VDC |
| Hot Swappable | Yes |
| Hot Redundancy | Supported |
| HTTPS | Supported |
| Network Services | IPv6, IP forwarding, service forwarding, network segmentation |
| Communication Services | Modbus TCP server, SNMP V1/V3, NTP V4 client/server |
| Cybersecurity | Built-in firewall, certificate authentication, RBAC, Syslog, IPSec |
| Width | 32 mm |
| Height | 131 mm |
| Length | 86.05 mm |
| Weight | 0.4 kg |
| Operating Temp | 0 to 60 deg C |
| Storage Temp | -40 to 85 deg C |
| Relative Humidity | 5 to 95% at 55 deg C, non-condensing |
| Protection Rating | IP20 |
| Origin | US |
| Certifications | CE, cULus, RCM, UKCA, EAC, Merchant Navy |
Modicon M580 Ethernet and OPC UA Communication
The BMENUA0100 occupies one Ethernet/X-bus rack slot and communicates through the M580 Ethernet backplane. Its front Ethernet interface supports 10/100/1000 Mbit/s operation. The embedded OPC UA server supports up to 10 client connections, with up to 40 subscriptions per session.
Standard OPC UA operation provides a minimum publishing interval of 250 ms and a minimum sampling interval of 125 ms. Fast sampling supports a 20 ms minimum sampling interval and 20 ms minimum publishing interval. The module supports up to 100,000 OPC UA nodes.
Network functions include IPv6, IP forwarding, service forwarding, network segmentation, Modbus TCP diagnostics, SNMP V1/V3 network management, and NTP V4 time synchronization. Security functions include HTTPS, certificate-based authentication, role-based access control, Syslog, IPSec, built-in firewall functions, and network physical isolation.
Frequently Asked Questions
Q: Can the BMENUA0100 be installed while the M580 rack remains powered?
A: Yes. The module supports hot swapping and configuration changes on the fly. Installation and replacement must follow the applicable M580 rack installation procedure.
Q: What is the electrical load of the BMENUA0100 on the rack power supply?
A: The specified current consumption is <= 140 mA at 24 VDC from the internal rack power supply.
Q: What Ethernet connection is provided for OPC UA communication?
A: The module provides one RJ45 Ethernet port supporting 10/100/1000 Mbit/s over double-shielded twisted-pair cabling. Ethernet backplane communication provides transparency between the module and connected M580 system components.
Field Installation Guidelines
Install the BMENUA0100 in an Ethernet or X-bus slot of the main rack, within the supported M580 X80 Ethernet backplane configuration. The module occupies one rack slot, with a maximum of two BMENUA0100 modules permitted per rack.
Route Ethernet cabling separately from high-voltage power conductors and high-current switching circuits where practical. Use the specified shielded twisted-pair Ethernet connection and maintain appropriate cable routing and bend-radius practices.
Connect the module only to the supported rack power system. Verify the rack power budget before installation, accounting for the module's <= 140 mA current consumption at 24 VDC.
Before commissioning OPC UA communication, configure IP addressing, network segmentation, certificates, user roles, and applicable firewall or IPSec functions according to the M580 cybersecurity configuration. Check the RUN, ERR, ETH MS, ETH NS, STS, and communication bus LEDs during startup and commissioning.
The module is rated IP20 and should therefore be installed inside the appropriate control enclosure. Maintain the specified 0 to 60 deg C operating temperature and avoid installation locations exposed to condensation or conductive contamination.
Pagamento: T/T, Western Union.
Porto de expedição: Xiamen.
Prazo de entrega: Normalmente, 1–3 dias úteis após a confirmação do pagamento (sujeito à disponibilidade em stock).
Entrega mundial: Enviamos peças de automação industrial para clientes em todo o mundo. Os custos de transporte são indicados no seu pedido de cotação.
Perguntas frequentes
Perguntas frequentes sobre orçamentos, envio, garantia e devoluçõesClique em Solicitar um orçamento na página do produto e envie-nos o número da peça, a quantidade necessária e o país de destino. A nossa equipa de vendas responderá com a disponibilidade atual, o preço e o prazo de entrega estimado.
Os artigos disponíveis em stock são normalmente preparados após o pagamento e a confirmação da encomenda. A maioria das encomendas é expedida do nosso armazém na China, embora o local de expedição possa variar consoante o stock disponível.
Sim. Enviamos peças de automação industrial para clientes em todo o mundo. O custo de envio e o tempo de trânsito dependem do destino, do peso da encomenda, do tamanho do produto e dos requisitos de importação locais.
Utilizamos habitualmente os serviços de correio expresso internacionais DHL, FedEx, UPS e outros. O transportador pode ser selecionado de acordo com o destino, a rapidez de entrega, o tamanho do envio e os requisitos do cliente.
Os nossos produtos estão geralmente cobertos por uma garantia de 12 meses. Os produtos elegíveis também podem ser devolvidos ao abrigo da nossa política de reembolso de 30 dias. Contacte a nossa equipa antes de devolver qualquer artigo para confirmar os termos aplicáveis e as instruções de devolução.
Também poderá gostar de
Publicações do blogue
Notícias sobre automação industrial, guias técnicos e atualizações de produtos.
