Configured for safety and process control in the Modicon M580 platform, the Schneider Electric BMEP584040S (BMEP584040S processor module) provides processor execution, Ethernet device communication, local and remote I/O management, and CIP Safety device processing. It supports up to 8 racks, 16 remote I/O stations, 64 distributed devices, and 64 CIP Safety I/O devices.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | BMEP584040S |
| Brand | Schneider Electric |
| Series | Modicon M580 |
| Product Type | Processor module |
| Origin | US |
| Weight | 0.849 kg |
| Dimensions | 9.921 x 7.008 x 3.504 in (package dimensions) |
| Operating Temp | -25 to 60 deg C |
| Storage Temp | -40 to 85 deg C |
| Power Consumption | 295 mA at 24 VDC |
| Supply | Internal power supply via rack |
| Rack Capacity | 8 racks |
| Local Discrete I/O | 4096 I/O |
| Local Analog I/O | 1024 I/O |
| Local Application-Specific Channels | 144 |
| Remote I/O Stations | 16 |
| Distributed Equipment | 64 |
| CIP Safety I/O Devices | 64 |
| Ethernet Connections | 1 service port + 2 device network ports |
| USB Connection | 1 USB mini-B |
| Program Memory | 16 MB |
| Data Memory | 2048 kB |
| Safety Program Memory | 4 MB |
| Safety Data Memory | 1024 kB |
| Flash Storage | 4 GB |
| Instruction Processing | 30 Kinst/ms at 65% Boolean + 35% fixed arithmetic; 40 Kinst/ms at 100% Boolean |
| Communication Services | RIO scanner, DIO scanner |
| Communication Module Capacity | 16 AS-Interface modules, 4 Ethernet communication modules |
| Protection Rating | IP20 |
| Protective Treatment | Conformal coated |
| Vibration Resistance | 3 gn |
| Shock Resistance | 15 gn |
| Relative Humidity | 5 to 95% at 55 deg C, non-condensing |
| Operating Altitude | 0 to 2000 m; 2000 to 5000 m with derating |
| Safety Level | SIL 3 IEC 61508/IEC 61511; SILCL 3 IEC 62061 and ISO 13849-1 Category 4; SIL 4 EN 50126/EN 50128/EN 50129 |
| Certifications | CE, UL, CSA, RCM, EAC, ATEX Zone 2/22, IECEx Zone 2/22, TÜV, UKCA |
| Cybersecurity Functions | DoS prevention, IPSec, SNMP logging, Syslog, audit trail, embedded firewall, firmware signature, password protection, port hardening |
M580 Ethernet and I/O Processing
The BMEP584040S uses Ethernet TCP/IP interfaces for service and device-network communication. The processor manages RIO and DIO scanning and supports distributed equipment and CIP Safety I/O devices. Local processing capacity is specified at 4096 discrete I/O and 1024 analog I/O, with up to 144 application-specific local channels.
Application-specific functions include counter processing, motion control, SSI encoder interfaces, accurate time stamping, serial links, and HART communication. The processor provides separate program, process data, safety program, and safety data memory areas.
Frequently Asked Questions
Q: How is the BMEP584040S powered?
A: The module receives its operating power through the Modicon M580 rack backplane. The specified current consumption is 295 mA at 24 VDC.
Q: What Ethernet connections are provided?
A: The processor has one Ethernet TCP/IP service port and two Ethernet TCP/IP device-network ports. A USB mini-B interface is also provided for integrated connections.
Q: What I/O and safety device capacity is specified?
A: The processor supports up to 4096 local discrete I/O, 1024 local analog I/O, 16 remote I/O stations, 64 distributed devices, and 64 CIP Safety I/O devices.
Field Installation Guidelines
- Install the processor in the specified Modicon M580 rack position and verify correct mechanical engagement with the backplane.
- Confirm that the rack power system can supply the processor and all connected modules within the applicable load limits.
- Route Ethernet communication wiring separately from high-current switching and power conductors where practical to reduce electromagnetic coupling.
- Terminate cable shields according to the applicable M580 installation and plant grounding design. Avoid creating unintended shield current paths.
- Verify Ethernet port assignment before connecting service and device-network cables.
- Check RUN, ERR, I/O, DL, BACKUP, Ethernet, SRUN, SMOD, and FORCED IO indicators during commissioning.
- Use the specified environmental limits when locating the rack. The module is IP20 and requires an enclosure providing the required environmental protection.
- For safety applications, verify the configured safety architecture, firmware compatibility, wiring, diagnostics, and safety validation procedure against the applicable M580 safety documentation before placing the system into service.
Pagamento: T/T, Western Union.
Porto de expedição: Xiamen.
Prazo de entrega: Normalmente, 1–3 dias úteis após a confirmação do pagamento (sujeito à disponibilidade em stock).
Entrega mundial: Enviamos peças de automação industrial para clientes em todo o mundo. Os custos de transporte são indicados no seu pedido de cotação.
Perguntas frequentes
Perguntas frequentes sobre orçamentos, envio, garantia e devoluçõesClique em Solicitar um orçamento na página do produto e envie-nos o número da peça, a quantidade necessária e o país de destino. A nossa equipa de vendas responderá com a disponibilidade atual, o preço e o prazo de entrega estimado.
Os artigos disponíveis em stock são normalmente preparados após o pagamento e a confirmação da encomenda. A maioria das encomendas é expedida do nosso armazém na China, embora o local de expedição possa variar consoante o stock disponível.
Sim. Enviamos peças de automação industrial para clientes em todo o mundo. O custo de envio e o tempo de trânsito dependem do destino, do peso da encomenda, do tamanho do produto e dos requisitos de importação locais.
Utilizamos habitualmente os serviços de correio expresso internacionais DHL, FedEx, UPS e outros. O transportador pode ser selecionado de acordo com o destino, a rapidez de entrega, o tamanho do envio e os requisitos do cliente.
Os nossos produtos estão geralmente cobertos por uma garantia de 12 meses. Os produtos elegíveis também podem ser devolvidos ao abrigo da nossa política de reembolso de 30 dias. Contacte a nossa equipa antes de devolver qualquer artigo para confirmar os termos aplicáveis e as instruções de devolução.
Também poderá gostar de
Publicações do blogue
Notícias sobre automação industrial, guias técnicos e atualizações de produtos.