Upozornit e-mailem, jakmile bude tento produkt dostupný
- Popis
- Reviews
- Doprava a platba
The BMXSDO0802 is an 8-channel safety digital output module in the Schneider Electric Modicon X80 I/O range, designed for Modicon M580 Safety controllers. It provides 24 VDC positive-logic semiconductor outputs for safety-related control signals. The module features non-isolated output channels, individual channel protection functions, and a 1.2 ms output response time.
Functional Description
The BMXSDO0802 switches 24 VDC field loads through eight semiconductor output channels. Positive logic defines the output switching arrangement, while the electronic output stage provides overload, overvoltage, short-circuit, and reverse-polarity protection.
The module supports a maximum current of 0.625 A per channel and a maximum module current of 10 A. These ratings must be considered together when allocating field loads and designing the output circuit.
Safety Architecture
The module is intended for use with a Modicon M580 Safety processor. It is part of the safety I/O architecture rather than a general-purpose output module for unrestricted use with standard controllers.
The supplied product information identifies TÜV Rheinland certification for safety applications, with capability levels specified under IEC 61508/61511, IEC 62061, ISO 13849, and railway safety standards. The applicable safety integrity or performance level depends on the system architecture, configuration, and application requirements; it should not be interpreted as an automatic SIL or performance-level rating for every installation.
Output Characteristics and Protection
The output response time is 1.2 ms. The maximum voltage drop in the ON state is less than 1.2 V, which should be considered when checking the voltage available at the connected field load.
Additional electrical characteristics include:
- Output parallel connection: permitted, maximum 2 outputs.
- Minimum resistive load impedance: 48 Ohm.
- Insulation resistance: greater than 10 MOhm at 500 VDC.
- Output voltage detection: below 14 VDC indicates a sensor fault; above 18 VDC indicates sensor OK.
- Reverse-polarity protection: blocking diode.
The module also provides a switching-frequency specification of 0.5/LI² Hz. This is retained as supplied; the exact interpretation should be checked against the manufacturer's technical documentation before using it to calculate switching limits.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | BMXSDO0802 |
| Brand | Schneider Electric |
| Product Type | Safety Digital Output Module |
| Product Range | Modicon X80 |
| Controller Platform | Modicon M580 Safety |
| Number of Outputs | 8 |
| Output Technology | Semiconductor |
| Output Logic | Positive |
| Nominal Output Voltage | 24 VDC |
| Output Voltage Range | 19-30 VDC |
| Nominal Current | 0.5 A |
| Maximum Current per Channel | 0.625 A |
| Maximum Module Current | 10 A (see editorial note) |
| Output Response Time | 1.2 ms |
| Maximum ON-State Voltage Drop | Less than 1.2 V |
| Minimum Resistive Load | 48 Ohm |
| Output Parallel Connection | Yes, maximum 2 outputs |
| Switching Frequency | 0.5/LI2 Hz |
| Insulation Resistance | Greater than 10 MOhm at 500 VDC |
| Voltage Detection Threshold | Less than 14 VDC: sensor fault; greater than 18 VDC: sensor OK |
| Reverse Polarity Protection | Blocking diode |
| Other Protection | Overload, overvoltage and short circuit |
| Dielectric Strength | 1500 VAC, 50/60 Hz, 1 minute, output/ground and output/internal logic |
| Safety Standards | IEC 61508, IEC 61511, IEC 62061, ISO 13849 |
| Railway Standards | EN 50126, EN 50128, EN 50129 |
| Certifications | TÜV Rheinland, CE, UL, CSA, RCM, EAC, UKCA |
| Protection Rating | IP20 |
| Protective Coating | Conformal coating |
| Operating Temperature | -25 to +60 deg C |
| Relative Humidity | 5-95% at 55 deg C, non-condensing |
| MTBF | 383,000 hours (manufacturer listing) |
| Dimensions | 32 x 131 x 86 mm |
| Weight | 0.12 kg |
| EAN | 3606481204929 |
| Lifecycle Carbon Footprint | 206 kg CO2 eq. |
Mounting and Connection
The BMXSDO0802 is installed on a Modicon X80 module carrier and secured with two screws. It supports a 20-pin removable terminal block connection, with cage-clamp, screw-clamp or spring-clamp terminal block options identified in the supplied product information.
The module is taller than a standard Modicon X80 Ethernet or X-Bus rack module. Rack clearance and module positioning should therefore be checked before installation.
Frequently Asked Questions
Q: Can the BMXSDO0802 operate with a standard Modicon M580 processor?
A: No. This is a safety output module intended for use with a Modicon M580 Safety processor. The safety controller and associated system configuration must support the module.
Q: Can two output channels be connected in parallel?
A: Yes. The manufacturer specifies parallel connection of up to two outputs. The connected load and applicable current limits must still be respected.
Q: Why can approximately 19 VDC be measured at an inactive output?
A: Internal polarization resistors support broken-wire detection. Schneider Electric confirms that a high-impedance voltage measurement on an unloaded, de-energized output does not necessarily indicate an active output. The OFF-state leakage current remains below 0.5 mA.
Sources and Editorial Notes
- Schneider Electric official product page: BMXSDO0802 Product Information.
- Schneider Electric Modicon M580 Safety System Planning Guide: Safety Module Technical Characteristics.
- Schneider Electric technical FAQ: Inactive Output Voltage Explanation.
Items requiring verification before publication:
- Maximum module current: The product specification lists 10 A, while the M580 Safety Planning Guide specifies a 5 A limit. The 10 A figure is retained from the product listing but should not be used as an installation design limit without confirmation.
- MTBF: The product description gives 382,097 hours, while the complementary specification lists 383,000 hours. The latter is used in the table.
- Switching frequency: The manufacturer's notation is retained without changing its electrical meaning.
Platba: T/T, Western Union.
Přístav odeslání: Xiamen.
Dodací lhůta: Obvykle 1–3 pracovní dny po potvrzení platby (v závislosti na skladových zásobách).
Celosvětové doručení: Dodáváme díly pro průmyslovou automatizaci zákazníkům po celém světě. Cena přepravy bude uvedena v naší nabídce na základě vaší poptávky.
Často kladené otázky
Časté otázky týkající se cenových nabídek, dopravy, záruky a vrácení zbožíNa stránce produktu klikněte na Požádat o cenovou nabídku a zašlete nám číslo dílu, požadované množství a cílovou zemi. Náš prodejní tým vám odpoví s informacemi o aktuální dostupnosti, ceně a odhadované době dodání.
Položky skladem se obvykle připravují po zaplacení a potvrzení objednávky. Většina objednávek se odesílá z našeho skladu v Číně, ačkoli místo odeslání se může lišit v závislosti na aktuálním stavu zásob.
Ano. Zasíláme díly pro průmyslovou automatizaci zákazníkům po celém světě. Náklady na dopravu a doba přepravy závisí na místě určení, hmotnosti zásilky, velikosti produktu a místních dovozních požadavcích.
Obvykle využíváme DHL, FedEx, UPS a další mezinárodní kurýrní služby. Dopravce lze vybrat podle místa určení, rychlosti doručení, velikosti zásilky a požadavků zákazníka.
Na naše výrobky se obecně vztahuje 12měsíční záruka. Způsobilé výrobky lze také vrátit v rámci našich 30denních podmínek pro vrácení peněz. Před vrácením jakékoli položky kontaktujte náš tým a ověřte si platné podmínky a pokyny k vrácení.
Mohlo by se vám také líbit