The Schneider Electric BMXDRA0805H is an 8-channel normally open (NO) relay discrete output module designed for the Modicon X80 common I/O platform, supporting Modicon M580 and Modicon M340 Programmable Automation Controllers (PAC). Engineered with conformal coating and an extended operating temperature range of -25 deg C to +70 deg C, this ruggedized module switches 24 to 240 V AC and 24 V DC loads in severe industrial environments.
Output Switching and Electrical Performance
The BMXDRA0805H provides 8 normally open relay output channels configured with positive discrete output logic. It accommodates a nominal load voltage range of 24 to 240 V AC (19 to 264 V AC operating limits) and 12 to 24 V DC (10 to 34 V DC operating limits), requiring a minimum switching load of 10 mA at 5 V DC to ensure reliable contact closure.
Backplane power draw is 79 mA typical at 3.3 V DC. Output switching response times are less than 10 ms for activation and less than 8 ms for deactivation, making the module suitable for general relay control of solenoids, contactors, and pilot indicators. Channel-to-bus isolation is rated at 2000 V AC (50/60 Hz for 1 minute) with an insulation resistance exceeding 10 MOhm at 500 V DC.
Ruggedized Construction and Environmental Ratings
The "H" suffix designates the hardened version featuring conformal coating on the internal printed circuit boards. This protective treatment enables continuous operation from -25 deg C to +70 deg C and up to 95% non-condensing relative humidity at 55 deg C.
The IP20-rated housing is qualified against corrosive and particulate contaminants under standard industrial classifications:
- Gas resistance: Class Gx and Class 3C4
- Dust and sand resistance: Class 3S4
- Salt mist resistance: Level 2
- Mold growth and fungal spore resistance: Class 3B2
Lifecycle Status and Replacement
Schneider Electric discontinued the BMXDRA0805H on July 1, 2022, with end-of-service scheduled for June 30, 2030. The official direct replacement is the Schneider Electric BMXDRA0815H, which retains the 8 NO relay output form factor and conformal coating while expanding the nominal DC switching capability to 24 to 125 V DC.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | BMXDRA0805H |
| Brand | Schneider Electric |
| Product Series | Modicon X80 |
| Product Type | Discrete Output Module |
| Compatible Controllers | Modicon M580, Modicon M340 |
| Number of Outputs | 8 NO Relay Outputs |
| Output Logic | Positive |
| Nominal Output Voltage | 24 to 240 V AC / 12 to 24 V DC |
| Operating Voltage Range | 19 to 264 V AC / 10 to 34 V DC |
| Minimum Switching Current | 10 mA at 5 V DC |
| Backplane Current Consumption | 79 mA typical at 3.3 V DC |
| Output Response Time | < 10 ms (activation), < 8 ms (deactivation) |
| Dielectric Strength | 2000 V AC at 50/60 Hz for 1 min |
| Insulation Resistance | > 10 MOhm at 500 V DC |
| MTBF | 2,119,902 hours |
| Protective Treatment | Conformal coating |
| Operating Temperature | -25 deg C to +70 deg C |
| Relative Humidity | 5% to 95% at 55 deg C (without condensation) |
| Enclosure Protection | IP20 |
| Certifications | ATEX, CE, CSA, EAC, IECEx, Merchant Navy, RCM, UL |
| Standards Compliance | EN 61131-2, EN 61000-6-4, EN 61000-6-2, EN 61010-2-201 |
| Net Weight | 0.145 kg |
Frequently Asked Questions
Q: What is the difference between the BMXDRA0805H and the standard BMXDRA0805?A: The "H" suffix indicates a hardened version with conformal coating, extending the operating temperature range to -25 deg C to +70 deg C and adding resistance to corrosive gases (Gx, 3C4), dust/sand (3S4), salt (Level 2), and mold/fungi (3B2).
Q: Can the BMXDRA0805H be replaced directly by the BMXDRA0815H?A: Yes. Schneider Electric designates the BMXDRA0815H as the official replacement for the discontinued BMXDRA0805H, offering the same 8 NO relay outputs and severe-environment coating while supporting an expanded 24 to 125 V DC load range.
Q: What is the minimum load required for reliable relay switching on the BMXDRA0805H?A: Each relay output requires a minimum switching current of 10 mA at 5 V DC to maintain proper contact reliability.
Оплата: T/T, Western Union.
Порт отгрузки: Сямынь.
Срок поставки: Обычно 1–3 рабочих дня после подтверждения оплаты (при наличии товара на складе).
Доставка по всему миру: Мы поставляем детали для промышленной автоматизации клиентам по всему миру. Стоимость перевозки указывается в вашем запросе на коммерческое предложение.
Часто задаваемые вопросы
Часто задаваемые вопросы о ценах, доставке, гарантии и возврате товаровНажмите Запросить предложение на странице товара и отправьте нам номер детали, необходимое количество и страну назначения. Наша команда продаж ответит, сообщив о текущем наличии, цене и предполагаемом сроке доставки.
Товары, имеющиеся в наличии, обычно подготавливаются после оплаты и подтверждения заказа. Большинство заказов отправляется с нашего склада в Китае, однако место отправки может варьироваться в зависимости от текущих запасов.
Да. Мы отправляем детали для промышленной автоматизации клиентам по всему миру. Стоимость и сроки доставки зависят от места назначения, веса посылки, размера товара и местных требований к импорту.
Мы обычно пользуемся услугами DHL, FedEx, UPS и других международных курьерских служб. Перевозчика можно выбрать с учётом пункта назначения, скорости доставки, размера отправления и требований клиента.
На наши товары обычно распространяется 12-месячная гарантия. Товары, соответствующие условиям, также можно вернуть в рамках нашей 30-дневной политики возврата средств. Перед возвратом любого товара свяжитесь с нашей командой, чтобы уточнить применимые условия и инструкции по возврату.
Вам также может понравиться
Публикации в блоге
Новости промышленной автоматизации, технические руководства и обновления продукции.