The GE IC200MDL940F is a 16-point relay output module in the VersaMax I/O product family. It provides individually isolated Form A (normally open) relay contacts for switching external AC and DC field loads. Its voltage-dependent contact ratings allow the module to handle different field circuit requirements, while individual channel indicators provide local output status information.
Output Configuration and Switching
The module uses 16 normally open mechanical relay contacts. Each output operates as a dry contact: the PLC output command controls relay operation, while the external field power supply provides the energy required by the connected load.
Individual channel isolation allows separate field circuits to be switched without sharing a common output reference. This is useful when different output points operate loads supplied from independent AC or DC circuits.
The relay contacts are rated for different current levels depending on the applied voltage:
- 5-265 VAC: maximum 2.0 A per point.
- 5-30 VDC: maximum 2.0 A per point.
- 31-125 VDC: maximum 0.2 A per point.
These ratings are specified for resistive loads. The 2.0 A rating must not be applied to the entire DC voltage range. Inductive loads also require consideration of contact switching stress and suppression requirements.
Switching Characteristics and Output Protection
The maximum ON and OFF response times are both 10 ms. This is a mechanical relay output rather than a high-speed semiconductor output, so it is intended for discrete switching rather than pulse-width modulation or rapid repetitive switching.
For inductive loads, the specified maximum switching frequency is 20 cycles per minute. The module does not include internal output fuses or snubber circuits. External overcurrent protection and suitable suppression components should be selected according to the connected load.
Individual point-status LEDs indicate the output states, while the OK indicator provides information about backplane power availability.
Backplane Power and Installation
The module draws its operating power from the VersaMax backplane, with a maximum specified 5 VDC current consumption of 490 mA. The external field supply provides the power switched through the relay contacts; the backplane supply should not be confused with the field-load supply.
An appropriate VersaMax I/O carrier is required for field wiring termination. Before installation or replacement, verify the carrier arrangement, terminal assignments, field supply voltage and contact-current requirements against the installed hardware configuration.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | IC200MDL940F |
| Brand | GE |
| Product Series | VersaMax |
| Product Type | Relay Output Module |
| Number of Output Points | 16 |
| Relay Contact Type | Form A, Normally Open (NO) |
| Relay Mechanism | Fixed coil, moving armature |
| Contact Material | Silver alloy |
| Output Voltage | 0-265 VAC; 0-125 VDC |
| Nominal Output Voltage | 120/240 VAC; 5/24/125 VDC |
| Maximum Load Current | 2.0 A per point (5-265 VAC); 2.0 A per point (5-30 VDC); 0.2 A per point (31-125 VDC) |
| Minimum Load Current | 10 mA per point |
| Channel-to-Channel Isolation | Individually isolated points |
| ON Response Time | 10 ms maximum |
| OFF Response Time | 10 ms maximum |
| Switching Frequency | 20 cycles per minute (inductive loads) |
| Output Voltage Drop | 0.3 V maximum |
| Output Leakage Current | Not applicable (open relay contact) |
| Backplane Power Supply | 5 VDC |
| Backplane Current Consumption | 490 mA maximum |
| External AC Field Supply Frequency | 47-63 Hz |
Frequently Asked Questions
Q: Can the IC200MDL940F switch different AC and DC voltage circuits simultaneously?
A: Yes. Its individually isolated relay contacts allow separate field circuits to use different AC or DC voltage sources, provided each circuit remains within the specified voltage and current ratings.
Q: What is the maximum DC switching current?
A: The maximum is 2.0 A per point at 5-30 VDC. For 31-125 VDC, the maximum decreases to 0.2 A per point. These ratings should be checked against the actual load characteristics.
Q: Does the IC200MDL940F provide built-in protection for inductive loads?
A: No. It does not include internal fuses or snubber circuits. External circuit protection and suitable transient suppression should be evaluated when switching relay coils, contactors or solenoid valves.
Plaćanje: T/T, Western Union.
Luka otpreme: Siamen.
Rok isporuke: Obično 1–3 radna dana nakon potvrde uplate (u zavisnosti od zaliha).
Isporuka širom sveta: Šaljemo delove za industrijsku automatizaciju kupcima širom sveta. Troškovi prevoza se navode u vašem RFQ-u.
Česta pitanja (FAQ)
Najčešća pitanja o ponudama, isporuci, garanciji i povraćaju robeNa stranici proizvoda kliknite na Zatražite ponudu i pošaljite nam broj dela, potrebnu količinu i zemlju odredišta. Naš prodajni tim će odgovoriti informacijama o trenutnoj dostupnosti, ceni i procenjenom roku isporuke.
Artikli koji su na stanju obično se pripremaju nakon uplate i potvrde porudžbine. Većina porudžbina šalje se iz našeg skladišta u Kini, iako mesto slanja može da varira u zavisnosti od trenutnog stanja zaliha.
Da. Šaljemo delove za industrijsku automatizaciju kupcima širom sveta. Troškovi i vreme isporuke zavise od odredišta, težine paketa, veličine proizvoda i lokalnih uvoznih zahteva.
Najčešće koristimo DHL, FedEx, UPS i druge međunarodne kurirske službe. Prevoznik se može izabrati u skladu sa odredištem, brzinom isporuke, veličinom pošiljke i zahtevima kupca.
Naši proizvodi uglavnom imaju garanciju od 12 meseci. Proizvodi koji ispunjavaju uslove mogu se takođe vratiti u okviru naše politike povraćaja novca u roku od 30 dana. Obratite se našem timu pre vraćanja bilo kog artikla da biste potvrdili važeće uslove i uputstva za povraćaj.
Možda će vam se dopasti i
Blog objave
Vesti iz industrijske automatizacije, tehnički vodiči i novosti o proizvodima.