Pređi na informacije o proizvodu
1 od 3

GE IS200ECTBG2ADE EX2100 Exciter Contact Terminal Board

11 na stanju
  • Manufacturer: General Electric
  • Product No.: IS200ECTBG2ADE
  • Product Type: EX2100 Exciter Contact Terminal Board
  • Condition: Potpuno nov
  • Payment: T/T, Western Union
  • Weight: 0.34 kg
  • Shipping port: Sjamен
  • Warranty: 12 meseci
  • Opis
  • Reviews
  • Dostava i plaćanje

The GE IS200ECTBG2ADE is an Exciter Contact Terminal Board for the EX2100 excitation control system. It provides field contact input monitoring and relay output interfaces between external equipment and the excitation controller. Designed for simplex operation, the board handles trip contacts, general-purpose relay outputs, and auxiliary contact signals using separate relay control and contact wetting voltages.

Functional Description

The ECTB provides electrical interfaces for contact signals associated with generator excitation control. Its relay outputs allow the controller to operate external circuits, while its contact input circuits monitor the status of customer-supplied auxiliary contacts.

The board includes two trip relay outputs and four general-purpose Form-C relay outputs. The latter provide normally open, normally closed, and common terminals for external circuit switching. Relay operation is controlled by the excitation controller through the EMIO interface.

Contact Input and Relay Configuration

The contact input circuits use a nominal 70 V DC wetting supply to detect external contact states. This arrangement allows the controller to monitor auxiliary contacts and dedicated generator status and lockout signals.

The distinction between the board's voltage ratings is important: 24 V DC supplies the relay control circuits, 125 V DC is the nominal customer supply for relay contacts, and 70 V DC provides contact wetting for input monitoring. These voltages serve different circuit functions.

Relay Contact Ratings

The general-purpose relay contacts use a customer-supplied DC power circuit. Their breaking capacity depends on the load type and operating voltage, rather than being represented by a single universal current rating.

According to the EX2100 control guide, the general-purpose relay contact characteristics include:

  • Resistive load: 2 A at 28 V DC or 0.5 A at 125 V DC.
  • Inductive load: 1 A at 28 V DC or 0.1 A at 125 V DC.
  • Inductive load rating is specified at an L/R time constant of 0.007 s.
  • External suppression must be provided by the customer for inductive loads.

These ratings should be checked against the actual external load before connecting field circuits.

Technical Specifications

Parameter Specification
Model IS200ECTBG2ADE
Brand General Electric (GE)
Series EX2100
Product Type Exciter Contact Terminal Board
Operational Mode Simplex only
Trip Relay Outputs 2
General-Purpose Relay Outputs 4 Form-C
Auxiliary Contact Inputs 6
Dedicated Contact Inputs 52G, 86G
Relay Control Voltage 24 V DC
Customer Power 125 V DC nominal
Contact Wetting Voltage 70 V DC
Relay Break Characteristic 28 V DC
Weight 0.34 kg
Dimensions 150 x 76 x 90 mm

Simplex Configuration and System Interface

The ECTBG2 configuration is intended for simplex EX2100 control. Its contact signals are connected to the M1 controller, rather than being distributed across multiple controllers for redundant voting.

The distinction between ECTBG1 and ECTBG2 is important when identifying replacement hardware. ECTBG1 supports redundant control with a two-out-of-three relay voting arrangement, whereas ECTBG2 is designed for simplex operation. These configurations should not be treated as interchangeable.

Frequently Asked Questions

Q: Can the IS200ECTBG2ADE be used in a redundant EX2100 control system?

A: No. The ECTBG2 configuration is intended for simplex operation. The ECTBG1 version is used for redundant control and has a different controller interface and relay voting arrangement.

Q: What is the difference between the 24 V DC and 125 V DC supplies?

A: The 24 V DC supply operates the relay control circuits, while the nominal 125 V DC customer supply is switched through the relay contacts to external circuits. They perform different electrical functions and should not be interchanged.

Q: What is the purpose of the 70 V DC wetting voltage?

A: It provides the electrical excitation required to monitor external contact states. The board uses this voltage for auxiliary contact monitoring and dedicated 52G and 86G status inputs.

Plaćanje: T/T, Western Union.

Luka otpreme: Siamen.

Rok isporuke: Obično 1–3 radna dana nakon potvrde uplate (u zavisnosti od zaliha).

Isporuka širom sveta: Šaljemo delove za industrijsku automatizaciju kupcima širom sveta. Troškovi prevoza se navode u vašem RFQ-u.

Česta pitanja (FAQ)

Najčešća pitanja o ponudama, isporuci, garanciji i povraćaju robe

Na stranici proizvoda kliknite na Zatražite ponudu i pošaljite nam broj dela, potrebnu količinu i zemlju odredišta. Naš prodajni tim će odgovoriti informacijama o trenutnoj dostupnosti, ceni i procenjenom roku isporuke.

Artikli koji su na stanju obično se pripremaju nakon uplate i potvrde porudžbine. Većina porudžbina šalje se iz našeg skladišta u Kini, iako mesto slanja može da varira u zavisnosti od trenutnog stanja zaliha.

Da. Šaljemo delove za industrijsku automatizaciju kupcima širom sveta. Troškovi i vreme isporuke zavise od odredišta, težine paketa, veličine proizvoda i lokalnih uvoznih zahteva.

Najčešće koristimo DHL, FedEx, UPS i druge međunarodne kurirske službe. Prevoznik se može izabrati u skladu sa odredištem, brzinom isporuke, veličinom pošiljke i zahtevima kupca.

Naši proizvodi uglavnom imaju garanciju od 12 meseci. Proizvodi koji ispunjavaju uslove mogu se takođe vratiti u okviru naše politike povraćaja novca u roku od 30 dana. Obratite se našem timu pre vraćanja bilo kog artikla da biste potvrdili važeće uslove i uputstva za povraćaj.

Products FAQs

Možda će vam se dopasti i