Schneider Electric ATV71HD22N4 Altivar 71 Variable Speed Drive
Configured for precise speed and torque regulation of asynchronous and synchronous motors in three-phase electrical power architectures, the Schneider Electric ATV71HD22N4 (ATV71 Variable Speed Drive) provides direct physical/electrical execution. Operating within an input range of 380 VDC to 480 VAC across a 50/60 Hz frequency line, this unit converts line power into regulated output frequency spanning 0.1 to 599 Hz. Rated for a nominal output of 22 kW (30 hp) at 480 V, the assembly features an integrated EMC filter alongside a heavy-duty cooling heat sink to sustain maximum torque profiles under variable load conditions.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | ATV71HD22N4 |
| Brand | Schneider Electric |
| Origin | France |
| Weight | 21 kg |
| Dimensions | 230 mm x 420 mm x 236 mm |
| Operating Temp | -10 to 50 deg C (without derating) |
| Power Consumption | 22 kW (30 hp) output rating |
| Input Voltage Range | 380...480 VAC (-15% to +10%), 3-phase |
| Line Current | 42 A at 480 V / 50 A at 380 V |
| Continuous Output Current | 40 A at 4 kHz / 460 V |
| Maximum Transient Current | 72 A for 60 s / 79.2 A for 2 s |
| Output Frequency Range | 0.1...599 Hz |
| Switching Frequency | 1...16 kHz (4 kHz nominal) |
| Ingress Protection | IP20 |
| Analog Inputs | 1x differential voltage (+/-10 VDC), 1x current/voltage (0-20 mA / 0-10 VDC) |
| Analog Outputs | 1x software configurable (0-20 mA / 0-10 VDC) |
| Discrete Inputs | 7x 24 VDC programmable (LI1...LI6, PWR safety input) |
| Relay Outputs | 2x configurable logic relays (R1A/R1B/R1C NO/NC, R2A/R2B NO) |
| Integrated Protocol | Modbus RTU (RS 485), CANopen |
Backplane Bus & Deterministic Communications
The ATV71 drive architecture uses internal bus synchronization protocols to manage deterministic fieldbus exchanges and high-density I/O expansion. When interfacing with industrial networks via optional communication adapters (such as Modbus TCP, EtherNet/IP, or Profibus DP), the unit executes control commands while suppressing firmware flash compatibility errors. Internal signal routing ensures isolation between high-voltage power components and low-voltage control terminals, preventing cross-talk and field noise interference from compromising high-speed pulse feedback loops.
Frequently Asked Questions
Q: What are the torque limits and current specs for the PWR safety input terminal?
A: The PWR safety terminal functions as a dedicated Safe Torque Off (STO) circuit operating at 24 VDC with an input impedance of 1500 Ohm. Response time on the safety loop executes within 100 ms or less to remove power safely from the motor terminals.
Q: What power cable sizes and tightening torques are specified for main line connection?
A: Power supply and motor terminal connections (L1/R, L2/S, L3/T, U/T1, V/T2, W/T3) accept conductor sizes up to 50 mm2 (1/0 AWG) secured with a terminal torque setting of 12 N.m (102.2 lb.in). Control logic terminals accept 2.5 mm2 (14 AWG) wiring tightened to 0.6 N.m.
Q: Can the drive operate without current derating at high switching frequencies?
A: Standard operation uses a nominal 4 kHz switching rate. The drive allows frequency adjustments between 1 and 16 kHz, but operation above 4 kHz requires applying an automated current derating factor to manage heat sink thermal dissipation.
Field Installation Guidelines
- Mount the drive in a vertical orientation within +/- 10 degrees on a flat, non-combustible vertical support surface to ensure uninhibited natural convection across the heat sink cooling fins.
- Maintain clear ventilation paths surrounding the drive housing: ensure at least 100 mm of unobstructed space above and below the chassis for airflow exhaust.
- Ensure all motor leads consist of shielded cabling up to a maximum length of 100 m (or 200 m for unshielded cabling) to comply with integrated EMC filter limits and prevent high-frequency radiation.
- Establish direct PE (Protective Earth) low-impedance grounding connections using copper conductors rated for at least 75 deg C. Grounding connections must meet or exceed local electrical safety guidelines before applying line voltage across phase terminals L1, L2, and L3.
Plaćanje: T/T, Western Union.
Luka otpreme: Siamen.
Rok isporuke: Obično 1–3 radna dana nakon potvrde uplate (u zavisnosti od zaliha).
Isporuka širom sveta: Šaljemo delove za industrijsku automatizaciju kupcima širom sveta. Troškovi prevoza se navode u vašem RFQ-u.
Česta pitanja (FAQ)
Najčešća pitanja o ponudama, isporuci, garanciji i povraćaju robeNa stranici proizvoda kliknite na Zatražite ponudu i pošaljite nam broj dela, potrebnu količinu i zemlju odredišta. Naš prodajni tim će odgovoriti informacijama o trenutnoj dostupnosti, ceni i procenjenom roku isporuke.
Artikli koji su na stanju obično se pripremaju nakon uplate i potvrde porudžbine. Većina porudžbina šalje se iz našeg skladišta u Kini, iako mesto slanja može da varira u zavisnosti od trenutnog stanja zaliha.
Da. Šaljemo delove za industrijsku automatizaciju kupcima širom sveta. Troškovi i vreme isporuke zavise od odredišta, težine paketa, veličine proizvoda i lokalnih uvoznih zahteva.
Najčešće koristimo DHL, FedEx, UPS i druge međunarodne kurirske službe. Prevoznik se može izabrati u skladu sa odredištem, brzinom isporuke, veličinom pošiljke i zahtevima kupca.
Naši proizvodi uglavnom imaju garanciju od 12 meseci. Proizvodi koji ispunjavaju uslove mogu se takođe vratiti u okviru naše politike povraćaja novca u roku od 30 dana. Obratite se našem timu pre vraćanja bilo kog artikla da biste potvrdili važeće uslove i uputstva za povraćaj.
Možda će vam se dopasti i
Blog objave
Vesti iz industrijske automatizacije, tehnički vodiči i novosti o proizvodima.